CHAPTER
En 300 RULES FOR ELECTRIC SERVICE
REVISION
NOTE:
Document #14101, effective 10-22-24,
adopted Chapter En 300 titled “Rules for Electric Service.” Document #14101 was adopted pursuant to RSA
12-P:5, IV RSA 362:2, II, RSA 365:6, RSA 370:1-9, RSA 374:1, 4, 5, 15, 39 and
49 and RSA 374-F:23, I to the extent the provisions apply under the authority
of the Department of Energy.
Pursuant to 2021, 91:187, effective
7-1-21, the Department of Energy (Department) was established by the adoption
of RSA 12-P. Pursuant to RSA 12-P:11, “All
of the functions, powers, duties, records, personnel, and property of the
public utilities commission incorporated in the statutes establishing the
department of energy and which replace the authority of the commission with the
authority of the department of energy, are hereby transferred, as of July 1,
2021, to the department of energy.”
Pursuant to RSA 12-P:14, “Existing rules, orders, and approvals of the public
utilities commission which are associated with any functions, powers, and
duties, transferred to the department of energy pursuant to RSA 12-P:11 or any
other statutory provision, shall continue in effect and be enforced by the
commissioner of the department of energy until they expire or are repealed or
amended in accordance with applicable law.”
Chapter En 300 applies to electric
service in the state by adopting various rules in the former Chapter Puc 300 of
the Public Utilities Commission (Commission) regarding meter reading and meter
accuracy and testing, service quality including voltage variation and
interruption of service, notice to the Department of accidents and outages, and
the requirement that utilities submit periodic reports for Department review. The Department adopted the existing sections
of the Puc 300 rules where the Department’s statutory authority existed. In some places of the En 300, the Department
clarified language which was retained from the existing Puc 300 rules. The Department has amended the text of the former
Puc 300 rules pertaining to master metering as set forth in En 303.01 to
specify the exceptions to individual metering and the circumstances where a
utility would be permitted to install or provide electric service to a master
meter. The Department has updated existing Commission forms where those forms
are now considered to be Department forms as referenced in En 308 and other
sections of Chapter En 300. The
Department has updated the references to publications in Appendix B and
throughout Chapter En 300.
The Commission subsequently readopted
with amendments Chapter Puc 300 titled “Rules for Electric Service” in Document
#14106, effective 10-25-24. Amendments included, but were not limited to, the
deletion of existing provisions in Chapter Puc 300 which Document #14101 had
adopted in Chapter En 300. See the Revision Note at the chapter heading for
Chapter Puc 300 for the filings affecting the former Chapter Puc 300.
PART
En 301 APPLICATION OF RULES
En 301.01 Application of Rules.
(a)
This chapter shall apply to any utility as defined by En 302.23 except
as provided in (b) below.
(b)
This chapter, except for En 307.01, shall not apply to any rural
electric cooperative for which a certificate of deregulation is on file
pursuant to RSA 301:57.
Source. #14101, eff
10-22-24, EXPIRES: 10-22-34 (see Revision Note at chapter heading for En 300)
PART
En 302 DEFINITIONS
En 302.01 “Commission” means the New Hampshire public
utilities commission.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.02 “Creep” means a condition where the rotor of
a mechanical meter rotates continuously when rated voltage is applied and the
load terminals are open circuited.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.03 “Customer” means any person, firm,
corporation, cooperative marketing association, utility, governmental unit, or
subdivision of a municipality or of the state or nation, supplied with electric
service by any utility.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.04 “Demand” means the average power measured over
a specified interval of time.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En. 302.05 “Department” means the New Hampshire
department of energy.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.06 “Electronic indicating demand device” means
an indicating device that determines demand values based on electronic pulse
inputs from an auxiliary device to a solid state circuit designed to calculate
and display demand quantities in conjunction with a timing signal derived from
the line frequency or a crystal oscillator timing circuit.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.07 “Electronic meter” means a meter that has
measurement circuitry built primarily of solid state electrical components.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.08 “Electric service” means the delivery of
electricity to a customer in this state by a utility.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.09 “Energy conservation” means energy use
activities that cost less to implement than the value of the resources saved.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.10 “Full load” means the meter accuracy test
point at rated test voltage, rated test current, and 1.0 power factor.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.11 “Independent System Operator for New England
(ISO-NE)” means the administrator or operator for New England’s bulk power
system or any successor system as named by the Federal Energy Regulatory
Commission (FERC).
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.12 “Indicating demand device” means a type of
metering equipment used to measure and display demand values.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En
302.13 “Light load” means the
meter accuracy test point at rated test voltage, 10% of rated test current, and
1.0 power factor.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.14 “Master metering” means the use of a single
meter to supply electric service at a building that contains 2 or more
premises.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.15 “Mechanical indicating demand device” means a
device which uses either mechanical thermal elements or mechanical gearing in
conjunction with a demand interval timing motor to determine demand values.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.16 “Mechanical meter” means a watt-hour meter
built with a stator and rotor assembly that operates via electromagnetic
induction principles.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.17 “Meter” means a device installed for the
measurement of electrical quantities to be used as a basis for determining
charges for electric service.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.18 “Power factor” means “power factor” as
defined in the Institute of Electrical and Electronic Engineers (IEEE), IEEE
141-1993 “Recommended Practice for Electric Power Distribution for Industrial
Plants,” section 8.2.1, dated 4/29/1994, available as noted in Appendix B.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.19 “Power factor load” means the meter accuracy
test point at rated test voltage, rated test current, and 0.5 lagging power
factor.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.20 “Recording demand device” means separate
equipment used to record electronic pulse inputs from an auxiliary device in
measured time intervals where the timekeeping signal is derived from the line
frequency or a crystal oscillator timing unit.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En
302.21 “Register constant” means the
factor by which the register reading is multiplied to convert the displayed
register readings in kilowatt hours or other units taking into consideration
the watt-hour constant, gear ratios, electronic register programming constants,
and instrument transformer ratios as necessary.
This term includes “dial constant,” “register multiplier,” or “reading
multiplier.”
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.22 “Root mean square (RMS)” means the measure of
steady-state voltage or current as calculated from the square root of the mean
of the squares from the voltage or current waveform.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.23 “Utility” means any public utility, as
described in RSA 362:2, owning, operating, or managing any plant or equipment
or any part of the same for the transmission, distribution, or generation of
electricity ultimately sold to the public within New Hampshire except:
(a)
Municipal corporations, to the extent exempt pursuant to RSA 362:4-a;
(b)
Entities specifically described as exempted pursuant to RSA 362:4-c; and
(c)
Competitive energy suppliers that have not requested public utility
status pursuant to RSA 374-F:7, I.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 302.24 “Wide-scale emergency” means an event which
results in, or is or expected to result in:
(a)
A sustained interruption of electric service to 10% or more of the
utility’s customers, or 40,000 of the utility’s customers, whichever is less
and restoration of electric service to any of these customers takes more than
24 hours; or
(b)
The federal, state, or local government declaring an official state of
emergency in the utility’s service territory and the emergency involves an
interruption of electric service.
Source. #14101, eff
10-22-24, EXPIRES: 10-22-34 (see Revision Note at chapter heading for En 300)
PART En 303 SERVICE PROVISIONS
En 303.01 Master Metering.
(a)
No utility shall install or provide electric service to a master meter
where individual metering is required by either the state building code adopted
by RSA 155-A:1, IV, in particular, the state adopted edition of the
International Building Code and the International Energy Conservation Code, or
by local amendments adopted pursuant to RSA 155-A:3 or local ordinances,
unless:
(1) Individual meter sockets have been installed
either by the utility or its customer;
(2) Any charge for electricity sold is measured
using a utility revenue grade meter and billed by the utility; and
(3) The utility’s tariff requires:
a. Electricity to be used on the premises to
which it is delivered; and
b. Prohibits the utility’s customer from
selling, assigning, or otherwise directly or indirectly disposing of the
electricity delivered to the master meter to others except through its
inclusion in a fixed rent.
(b)
A utility may install or provide electric service to a master meter where
individual metering is not required by the state building code adopted by RSA
155-A:1, IV, in particular, the state adopted edition of the International
Building Code and the International Energy Conservation Code, only when:
(1) Local amendments or regulations adopted by
ordinance pursuant to RSA 155-A:3 do not prohibit master metering;
(2) Any installation of individual meters by the
property owner are not used for billing for electricity use; and
(3) The utility’s tariff requires:
a. Electricity to be used on the premises to
which it is delivered; and
b. Prohibits the utility’s customer from
selling, assigning, or otherwise directly or indirectly disposing of the
electricity delivered to the master meter to others except through:
(i) Its inclusion in
a fixed rent; or
(ii) Through
an unmetered sharing of expense arrangement where 2 or more businesses jointly
utilize the same premises and service is rendered through a single service
connection and meter.
(c)
For the purposes of this part, the sale of electric vehicle charging
services to a third party from an electric vehicle charging station shall not
be considered the resale of electricity.
(d)
The restrictions against installing or servicing a master meter in En
303.01(a) and (b) shall not apply where the master meter would have been
permitted pursuant to a commission rule in effect at the time the master meter
was installed, or master metering was permitted by a decision issued by the
commission or department prior to January 1, 2025, and:
(1) Building permits have been obtained and
occupancy approvals are in effect for the subject building;
(2) The design and use of the building has not
changed since installation, if installed pursuant to a commission rule, or
since issuance of a decision by the commission or department permitting the
master meter; and
(3) The utility’s customer remains in conformity
with any conditions imposed by a decision of the commission or department.
(e)
The utility shall require its customers to:
(1) Certify their eligibility for master
metering;
(2) Provide documentation necessary to verify
that the customer complies with En 303.01(a) or (b) before providing initial
service to the customer; and
(3) Certify their eligibility for master metering
and whenever a material change occurs in building use, billing practice, or
electrical design, or a change is made to a building code or zoning ordinance
relating to metering occurs provide documentation necessary to verify that the
customer continues to meet En 303.01(a) or (b) and is grandfathered with
respect to any change in code or ordinance.
(f)
Notwithstanding any other department rule to the contrary, the
department shall not waive any of the provisions of this part.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 303.02 Meter Reading.
(a)
The customer shall be provided metering equipment for each service
location which measures or provides information to determine the following:
(1) The number of kilowatt-hours (kWh)
registered; and
(2) If applicable, the following:
a. Kilowatt (kW) demand;
b. Kilovolt amperes (kVA) demand; and
c. Kilovolt-ampere reactive (kVAr)
demand.
(b)
A utility shall plainly mark the meter constants on a visible surface or
base of all its meters which show the watt-hours per revolution of the meter
disk or the electronic equivalent applicable to an electronic meter.
(c)
A utility shall plainly mark on a visible surface or base of all its
meters the register constant if the register constant is not one.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
PART
En 304 QUALITY OF ELECTRIC SERVICE
En 304.01 Frequency. A utility shall provide alternating current
distribution systems which shall have a design and operating frequency of 60
cycles per second under normal system conditions which shall vary only within a
narrow range according to operations criteria established by the ISO-NE.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 304.02 Voltage Variation.
(a)
For purposes of this section, “Y” means the 4-wire connection type used
for a particular 3 phase electric system component.
(b)
Each utility furnishing electric service shall adopt a standard nominal
average RMS voltage or voltages which are consistent with the design of the
distribution system for its entire service area and for each of the districts
or zones into which the distribution system or systems are divided from one of
the following systems:
(1) For secondary voltages of 120 and 120/240
volts, single phase 2-wire or 3-wire systems; or
(2) For secondary voltages of 120/208Y, 240,
277/480Y, 480, and 600 volts, 3-phase, 3-wire, or 4-wire systems.
(c)
A utility shall maintain the nominal secondary voltage at the utility’s
service terminals or at the street lamp in the case of multiple street
lighting, as installed for each customer, within plus or minus 5% average RMS.
(d)
When a customer receives service from primary distribution voltage and
is responsible for supplying its own voltage regulation, the utility shall
maintain the nominal secondary voltage at the utility’s service terminals as
installed for each customer, within plus or minus 10% RMS, except as provided
in (e) below.
(e)
When a customer is not responsible for its own voltage regulation, the
utility shall maintain the nominal average RMS voltage at the utility’s service
terminals, as installed for each customer, within plus or minus 5%.
(f)
The requirements of (d) and (e) above shall not apply to transactions
between utilities provided that primary customer voltage requirements are
maintained.
(g)
Voltage variations outside of the limits in (c), (d), and (e) shall be
allowed in accordance with ANSI C84.1-2020 “Electrical Power Systems Voltage
Ratings (60Hz),” dated 3/10/2020, available as noted in Appendix B.
(h)
A utility may vary from the voltage requirements provided by this
section in a special contract provided that:
(1) The permissible variation in voltage for
service shall be specifically mentioned in the contract; or
(2) A statement is included in the contract to
indicate that the contracting parties are in agreement concerning the allowable
variation.
(i) When voltage measurements for detecting
variations are required, a utility shall make the measurements at the utility’s
service terminals, or at the street lamp in the case of multiple street
lighting, unless otherwise agreed to by the customer and the utility.
(j)
If voltage measurements are taken at places other than at the utility’s
service terminals or at the street lamp in the case of multiple street
lighting, those measurements shall be corrected to the utility’s service
terminal or street lamp in the case of multiple street lighting.
(k)
The utility shall maintain the voltage and frequency delivered at the
utility’s service terminals or at the street lamp in the case of multiple
street lighting, pursuant to En 304.01 and En 304.02(b), (c), (h), and (i).
(l)
Voltage outside the limits specified in this section shall not be
considered a violation of this section when such variations:
(1) Arise from adverse weather conditions;
(2) Arise from operation of the affected
customer’s equipment at low power factor;
(3) Arise from unbalanced operation of the
affected customer’s equipment;
(4) Arise from failure of, or emergency
maintenance on, equipment;
(5) Are transient events on a system designed to
good utility practice, as defined in En 306.01(b), arising from operation of
system equipment during system protection, control, and switching activities;
(6) Are caused by emergency system operating
conditions or order of the independent system operator; or
(7) Arise from actions of others.
(m)
A voltage variation shall not be considered a violation of this section
if:
(1) The variation does not occur more than once
per day; and
(2) Does not exceed 2 minutes in duration.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 304.03 Interruptions of Service.
(a) Each utility shall use all reasonable means
within industry practices to avoid interruptions to service, including:
(1) Maintaining appropriate levels of
maintenance;
(2) Planning for unexpected events; and
(3) Considering in decisions affecting potential
interruptions to service:
a. The potential safety, reliability, cost, and
delay issues; and
b. The manner that best accommodates the public.
(b)
If an interruption to service occurs, the utility shall restore service
within the shortest time reasonable, consistent with safety, and provide
service on a 24-hour basis.
(c)
Each utility shall maintain a record, as required in (d) below, when an
interruption to service of more than a 5-minute duration occurs affecting:
(1) An entire substation; or
(2) The entire distribution circuit of a
substation.
(d)
When an interruption to service occurs as described in (c) above, a
utility shall:
(1) Keep a record of the circumstances of the
interruption; and
(2) Report the interruption to the department on
Form E-2, pursuant to En 308.02.
(e)
When service is interrupted to perform work on lines or equipment, the
utility shall conduct such work at a time causing minimum inconvenience to
customers consistent with the circumstances.
(f)
A utility shall attempt to notify all affected customers in advance of
all planned interruptions to service.
(g)
When a utility has actual notice of customers known by the utility who
would encounter a potentially life-threatening situation as a result of a
planned service interruption, the utility shall provide actual notice to those
customers of planned service interruptions.
(h)
A potentially life-threatening situation, for purposes of (g) above,
shall mean a situation where:
(1) A customer relies upon life support
equipment; or
(2) Any other potentially life-threatening
medical condition exists.
(i) A utility shall be permitted to require the
customer to document the potentially life-threatening situation and to request
such documentation be updated on an annual basis.
(j)
A utility shall interrupt or curtail electric service or vary the
characteristics thereof under the following circumstances:
(1) When necessary to prevent injury to persons
or damage to property;
(2) When directed or requested to do so by
police, fire, or other public safety officials;
(3) When required by conditions occurring in the
interconnected transmission grid connected to its facilities, to effect
temporary load reduction for the common good; or
(4) With notice to the customers or group of
customers and the department pursuant to En 1203.11, to prevent a single
customer or group of customers from causing continuing adverse effects to the
electricity supply of another customer or group of customers.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 304.04 Voltage Complaints.
(a)
Upon receipt of a customer voltage complaint, a utility shall
investigate to determine whether the complaint was founded or unfounded.
(b)
For the purposes of this section:
(1) “Founded” means the utility’s determination
that the voltage complaint was based on a voltage variation in violation of En
304.02;
(2) “Unfounded” means the utility’s determination
that the voltage measures were within the limits established in En 304.02; and
(3) “Voltage complaint” means written notice to
the company or oral communication with the utility’s customer service
representatives by the customer of conditions or circumstances that suggest or
evidence voltage variations outside of the limits established in En 304.02.
(c)
When a utility determines that a voltage complaint is founded, it shall
take appropriate steps to correct the condition and bring voltage into the
limits established in En 304.02.
(d)
When a utility determines that a voltage complaint is founded or
unfounded, it shall provide written notification to the customer within 10
calendar days of such determination.
(e)
Each utility shall report voltage complaints on a monthly basis to the
department pursuant to En 308.01.
(f)
Each utility shall maintain all records of voltage complaints
investigated pursuant to (a) above for a period of 5 years from the date of the
complaint.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
PART
En 305 METER ACCURACY AND TESTING
En 305.01 Inspection of Meters.
(a)
A utility shall inspect all meters for correctness of register constant
before installing the meter on a customer’s premises.
(b)
No new watt-hour meter shall be placed into service unless specific test
results indicate a registration within the tolerances of En 305.02(a) below.
(c)
Paragraph (b) above shall not apply to electronic indicating demand
devices such as electronic recorders and internal electronic registers which
shall be subject to examination by utilities to assure that the devices have
not been modified in a way that affects performance.
(d)
A utility shall test each new watt-hour meter prior to installation.
(e)
A utility shall use one of the following methods to comply with (d)
above:
(1) Test all meters received from the
manufacturer;
(2) Conduct sample testing after department
approval of the sample testing methods; or
(3) Accept manufacturer testing data with
specific test results consistent with En 305.03(a) below.
(f)
Before returning a meter to service which has been removed from service
for any reason, a utility shall inspect and, if necessary:
(1) Repair the meter; or
(2) Recalibrate the accuracy of the meter.
(g)
A utility shall inspect all watt-hour meters and demand devices for
correctness of operation when installed, perform an electrical test of all
instrument transformer connections, and correct or repair such meters and
devices as necessary.
(h)
Prior to or at the time of installation of all instrument transformers,
a utility shall also conduct the following activities:
(1) Review and maintain manufacturer’s test data
for instrument transformers purchased;
(2) Verify the current transformer ratio and
voltage transformer ratio via electrical testing;
(3) Verify wiring by
performing an inspection of instrument transformer secondary circuit
connections consisting of:
a. Verification of polarity by using one of the
following methods:
1. Electrical testing where sufficient load
current exists; or
2. Visual
inspection of control cable wiring between the instrument transformer secondary
terminals and the meter terminals;
b. Verification that the current transformer
input signal phase matches the corresponding voltage or voltage transformer
input signal phase to the meter; and
c. Verification that phasing is appropriate
where multiple primary conductors exist for one or more phases that serve as
the primary windings for a window type current transformer; and
(4) Confirm the effective current transformer
ratio based on the nominal nameplate ratio for the connected secondary
terminals along with proper consideration for multiple primary conductor loops
in window type current transformer installations.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 305.02 Test and Calibration of Meters.
(a)
A utility shall test all watt-hour meters at loads and adjust to
tolerances as follows:
(1) At full load, the meter shall register within
plus or minus 1%;
(2) At light load, the meter shall register
within plus or minus 1%; and
(3) At power factor load, the meter shall
register within plus or minus 2%.
(b)
A utility shall test mechanical meters for creep by visual inspection of
the meter’s rotor or utilizing electronic test methods.
(c)
If the rotor does not move with rated voltage and no load current
applied to the meter, it shall be considered to have passed the test required
by (b) above.
(d)
If movement is detected in the rotor when rated voltage and no load
currents are applied to the meter, the movement shall be timed, and if the
results comply with the creep test guidelines of section 4.7.2.1. of ANSI
C12.1-2022 “Code for Electricity Metering,” dated 6/9/2022, available as noted
in Appendix B, it shall be considered to have passed the test required by (b)
above.
(e)
Meters which fail the creep test shall not be placed into service.
(f)
A utility shall test and adjust all indicating and recording demand
devices as follows:
(1) The utility shall verify that any indicating
demand device shall reset properly to zero when placed in service or allowed to
remain in service without adjustment;
(2) The utility shall, in order to determine the
accuracy of each mechanical indicating demand device, conduct an up-scale test,
meaning a test on the upper end or at the higher values of the scale of the
meter, as follows:
a. According to the meter manufacturer’s
specifications; or
b. If the meter manufacturer does not provide
specifications as to conducting an up-scale test, with a test conducted at a
minimum of one demand interval cycle, at a point near 1/2 scale;
(3) A utility shall not place in service or allow
to remain in service after inspection any mechanical indicating demand device
which has an error in indication of more than plus or minus 2% in full scale
registration without adjustment; and
(4) Recording demand devices shall conform to the
in-service requirements of ANSI C12.1-2022 “Code for Electricity Metering,”
dated 6/9/2022, available as noted in Appendix B.
(g) To determine the accuracy of
electronic indicating demand devices, each utility shall conduct a test at a
load and time interval that will result in a demand reading with resolution
sufficient to determine that the reading is within plus or minus 2% of the
average load applied to the meter during the test. For shipments of new self-contained single
phase or network demand meter purchases, the utility shall only be required to
test a sample of meters, consistent with En 305.01(e)(2), to verify the demand
related programming values are correct and that demand calculations are
performed correctly.
(h)
A utility shall test all motors used to maintain a timing cycle in a
mechanical indicating demand device to insure they are running at the proper
speed, where such timing cycle directly affects meter registration.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 305.03 Test Schedules for Watt-Hour Meters and
Demand Devices.
(a)
A utility may accept as a first test and record as a test a
manufacturer’s test on new meters if the meter is certified by the manufacturer
as built to comply with ANSI C12.1-2022 “Code for Electricity Metering” dated
6/9/2022, or ANSI C12.20-2015 “Electricity Meters,” dated 4/1/2017, available
as noted in Appendix B.
(b)
A utility shall test and calibrate all new meters not certified by the
manufacturer as provided in (a) above before placing any such meter into
service.
(c)
A utility shall each year test and, as necessary, repair and recalibrate
or retire all watt-hour meters and demand devices in service on a test schedule
as follows:
(1) All self-contained single-phase watt-hour
meters:
a. On a periodic basis resulting in each meter
being tested at least once every 12 years; or
b. By each year selecting, testing and, as
necessary, retiring meters under a plan as follows:
1. A sample test group, selected at random and
representing a cross-section of the utility’s meters, comprised of at least
0.5% of meters in use; and
2. An additional number of meters, determined
pursuant to (d) below, selected from those meters which appear to be most
adversely affecting meter accuracy;
(2) Self-contained polyphase meters, each meter
no less than once every 24 years;
(3) Single-phase transformer-rated meters, each
meter no less than once every 16 years; and
(4) Polyphase transformer-rated meters, each
meter no less than once every 8 years.
(d)
Each utility which tests self-contained single-phase watt-hour meters
pursuant to (c)(1)b. above, shall test and repair and recalibrate or retire
each year a minimum number of meters, pursuant to (c)(1)b.2. above, in addition
to sample meter tests required to be conducted pursuant to (c)(1)b.1. above,
according to the formula as follows:
(1) The utility shall create a test curve ratio
in which:
a. “X” means the percentage of meters in the
cumulative sample test group which tested outside of the weighted accuracy
limits of between 98% and 102% for mechanical meters and between 98% and 101%
for electronic meters; and
b. “R” means the percentage of the total number
of meters subject to sample testing which it shall test and repair and
recalibrate or retire in addition to those meters tested pursuant to
(c)(1).b.1. above; and
(2) Each utility shall determine the number of
additional meters it shall test pursuant to this paragraph by calculating “R”
as described below and applying this percentage to the total number of
in-service meters subject to sample testing, as follows:
a. When “X” is between 0% and 3%, by multiplying
12.5 by “X” divided by 3, squared, as in the formula below:
R = 12.5(X/3)2 percent;
b. When “X” is greater than 3% and less than 6%
by subtracting from 25, 12.5 multiplied by 2 minus “X,” divided by 3, squared,
as in the formula below:
R = 25 - 12.5(2 -
X/3)2
percent;
c. When “X” is greater than 6%, “R” shall equal
25%;
d. If “X” is 0.0% to 0.5%, the number of the
additional meters to be tested shall be multiplied by 1.0; and
e. If “X” is greater than 0.5%, the number of
additional meters to be tested shall be multiplied by 1.0 + ((X – 0.5)/2).
(e)
A utility shall include in the cumulative sample required by (d)(1)a.
above:
(1) The sample test group of the current year;
and
(2) To the extent available, the sample test
groups of the immediately preceding 3 years.
(f)
In determining the minimum number of additional meters which it shall be
required to test pursuant to (c) above, a utility shall not include any meter
returned to the shop for maintenance.
(g)
A utility shall notify the department in writing before changing any
meter testing schedule which the utility has adopted pursuant to this section.
(h)
A utility shall test and recalibrate as necessary all polyphase meters
removed from service before returning the meter to service.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 305.04 Request Tests and Reports and Records of
Meter Tests.
(a)
When a customer requests that a utility test the customer’s meter, the
utility shall test the accuracy of the customer’s meter within 15 calendar days
from the time this request is made.
(b)
A utility may require the deposit of a fee of not more than $20.00 for
such a test and shall, in cases where a customer presents evidence of financial
hardship as defined in En 1202.10, either waive the fee or offer the customer
the opportunity to enter into a payment plan for such fee.
(c)
A utility shall conduct any test on a meter requested by the customer
with the meter in its service location.
(d)
If, on testing, as described in (a) above, the meter is found to have an
average error greater than 2%, the utility shall promptly refund the deposit to
the customer.
(e)
If the meter, upon testing as described in (a) above, is not found to
have an average error greater than 2%, the utility may retain the amount
deposited for the test.
(f)
A utility shall allow a customer to be present or to be represented by
an agent who the utility shall permit to be present when the utility conducts
the test on that customer’s meter.
(g)
The utility shall report the results of the meter test to the customer
within 15 calendar days of the test.
(h)
In the report required by (g) above, the utility shall provide:
(1) The name of the customer requesting the test;
(2) The date of the request;
(3) The location;
(4) The type, make, and the serial number of the
meter;
(5) The date tested;
(6) The numeric result of the weighted-average
test;
(7) The numeric range of weighted-average test
results permitted by the department; and
(8) A statement indicating whether the customer’s
test result was within or outside the range permitted by the department.
(i) When a utility has received a request for a
meter test, the utility shall not remove the meter from the customer’s premises
or interfere with or adjust the meter to be tested unless it has first
obtained:
(1) The written consent of the customer; or
(2) A waiver of the consent requirement pursuant
to En 201.05.
(j)
When a customer requests that the department verify the accuracy of the
customer’s meter, the department shall, by a representative, monitor the
conducting of a meter test conducted by the utility.
(k)
Each utility shall submit to the department reports of periodic and
sample tests of meters on Form E-3 and Form E-3A once a year pursuant to En
308.03 and En 308.04.
(l)
Each utility shall submit to the department quarterly reports containing
monthly data of customer requests for meter tests on Form E-4 pursuant to En
308.05.
(m)
A utility shall retain in its files a complete record of the last test
made on each meter.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 305.05 Customer’s Bill Adjustments.
(a)
In meter tests made by the utility pursuant to En 305.04, the utility
and the department shall judge the correctness of registration of the meter and
its performance in service by its average error.
(b)
A utility and the department shall determine average error for purposes
of meter tests as follows:
(1) If the meter is used to measure a load which
is constant, such as a street lighting load or a display sign load, the meter
shall be tested at the constant load;
(2) The error of a meter used to measure a
constant load shall be accepted as the average meter error;
(3) If the meter is used on a varying load, the
average error shall be:
a. The weighted average of its error at light
load with a weighting of 1.0; and
b. The weighted average of its error at full
load with a weighting of 4.0; and
(4) Any adjustment of charges which is made in
accordance with this section shall be based on the average error as determined
by this paragraph.
(c)
Whenever, as the result of a test made by the utility, a watt-hour meter
is found to have an average error greater than 2%, the company shall, except to
the extent provided in (d) below, refund to the customer an amount equal to the
charge for the excess kilowatt-hours billed for a period:
(1) Equal to 1/2 the time elapsed since the last
test; or
(2) If the time when the error first developed or
occurred can be definitely fixed, then from that point.
(d)
The calculation for a bill adjustment in (c) above shall not consider
any period during which:
(1) The customer did not receive service at that
location; or
(2) The customer was purposefully diverting
electricity or tampering with the metering installation.
(e)
Whenever, as the result of a test made by the utility, a watt-hour meter
is found to have an average error greater than 2%, the company may bill the
customer for the unbilled kilowatt-hours supplied for the shorter of the
following periods:
(1) The previous 6 months of active usage; or
(2) The period since the last test.
(f)
When a customer is charged pursuant to (e) above, the utility shall
allow the customer to request a payment plan, and regardless of the customer’s
financial circumstances, such payment plan shall not be less than the period of
time over which the unbilled kilowatt-hours accrued unless agreed to by the
utility and the customer.
(g)
If a meter is either not registering or partially registering the
electricity delivered to the customer, the utility shall base the bill for the
period of non-registration or partial registration upon:
(1) Information recorded by a meter properly
registering usage at that location prior or subsequent to the period of
non-registration or partial registration; and
(2) Any other pertinent information supplied by
the customer or known to the utility.
(h)
When calculating the difference between the billed and estimated amounts
resulting from the non-registration or partial registration, the utility shall
not bill the customer for more than 6 months of partial or non-registration
unless the customer was purposely diverting electricity or tampering with the
metering installation.
(i) The utility shall provide each customer
receiving a refund pursuant to (c) above or being charged pursuant to (e) above
with a clear explanation of how such refund or charges were calculated.
(j)
If a meter is determined to have been assigned to the wrong customer and
a customer has been billed based on usage recorded on a meter connected to
residential or commercial space not occupied by that customer, the utility
shall correct the billing to affected customers as follows:
(1) For customers who have been under billed,
invoices for the billing difference shall cover the customer’s period of
occupancy or 6 months, whichever is shorter; and
(2) For customers who have been overbilled,
refunds of the billing difference shall cover the period of occupancy or 24
months, whichever is shorter.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 305.06 Testing Facilities and Equipment,
Watt-Hour Standards.
(a)
Every utility shall have available one or more reference standards for
the sole purpose of checking working standards.
(b)
Each utility shall have all reference standards and all working
standards certified at least once each year in a laboratory meeting
specifications recommended by the watt-hour standard manufacturer.
(c)
Each utility shall have each working standard which it maintains
accompanied by a calibration card noting the corrections at various working
loads.
(d)
Each utility shall keep on file in its office for 2 years any
calibration cards which have been superseded.
(e)
Each utility shall maintain an adequate number of working standards for
testing customer meters.
(f)
Each utility shall check the mechanical field working standards used in
the direct calibration of customer meters every 3 months to determine whether
there has been a change in the performance of a standard unless the mechanical
field working standard is certified at intervals recommended by the
manufacturer not to exceed one year.
(g)
Each utility shall check the mechanical meter shop working standards
used in the direct calibration of customer meters once a week to determine
whether there has been a change in the performance of the standard, and shall
certify the mechanical meter shop working standard at intervals recommended by
the manufacturer not to exceed one year.
(h)
Each utility shall compare its electronic working standards for testing
customer meters to reference standards at least once every year.
(i) Any working standard found to be in error by
more than 1% shall be removed from service.
(j)
A utility shall certify its watt-hour standards as follows:
(1) In an independent standards laboratory; or
(2) In a laboratory maintained by the utility
provided that the department accepts the instruments and methods pursuant to En
201.05.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 305.07 Testing Facilities and Equipment, Portable
Indicating Standards.
(a)
Every utility shall have available reference indicating electrical
instruments of suitable range for checking working instruments.
(b)
Each utility shall check reference indicating instruments required by
(a) above at least once each year in an independent standards laboratory.
(c)
Each utility shall not use the reference indicating instruments required
by (a) above in the field as working instruments.
(d)
Each utility shall have calibration cards accompany each instrument
required by (a) above which note the corrections to be applied at the various
parts of the working scale.
(e)
Each utility shall have available the types and quantities of working
instruments necessary to determine compliance with these rules for:
(1) Recording and indicating customer voltage;
and
(2) Testing any other electrical quantities which
may be necessary to comply with the measurement and reporting requirements of
this chapter.
(f)
Each utility shall check the working instruments required by (e) with
the reference instruments at least once each year.
(g)
If reference instruments are not available within the utility, the
utility shall have field instruments checked in an independent standards
laboratory meeting specifications recommended by the meter manufacturer in
intervals not to exceed one year.
(h)
A utility may certify its reference indicating standards in a standards
laboratory which it maintains provided that the instruments and methods meet
specifications recommended by the meter manufacturer.
(i) Pursuant to RSA 365:6, each utility shall,
upon request, provide the department access to its meter testing facilities and
any and all meter test results.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
PART
En 306 EQUIPMENT AND FACILITIES
En 306.01 Standard Practice in Construction,
Operation, and Maintenance.
(a)
Each utility shall construct, install, operate, and maintain its plant,
structures, and equipment and lines, as follows:
(1) In accordance with good utility practice;
(2) After weighing all factors, including
potential delay, cost, and safety issues, in such a manner to best accommodate
the public; and
(3) To prevent interference with other underground
and above ground facilities, including facilities furnishing communications,
gas, water, sewer, or steam service.
(b)
For purposes of this section, “good utility practice” means in
accordance with the standards established by:
(1) The C2-2023 “National Electrical Safety
Code,” 2023 Edition, available as noted in Appendix B;
(2) When applicable, the International Energy
Conservation Code 2018 as adopted pursuant to RSA 155-A:1, IV; and
(3) The ISO-NE.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 306.02 Joint Pole Construction. Each utility involved in any installation
which makes use of poles either for single or joint occupancy shall conform its
construction, installation, operation, and maintenance to the requirements of
En 306.01.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 306.03 Electrical Interference.
(a)
Each utility shall make a full and prompt investigation of complaints
made by the utility’s customers or by the general public involving electrical
interference with reception by communications equipment in the proximity of the
utility’s transmission and service areas, including but not limited to
interference with television and radio reception.
(b)
Each utility shall maintain a record of complaints which it receives
pursuant to (a) above.
(c)
Each utility shall report to the department all complaints, as described
in (a) above, that it receives that are not resolved to the satisfaction of the
complaining party within 30 days of receipt or notification of the complaint.
(d)
The report referred to in (c) above shall include the location of the
complaint, the circuit number of the line, and a brief description of the
interference.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 306.04 Safety Instructions. Each utility, in the operation, construction,
or maintenance of its plant and facilities, shall:
(a)
Develop and implement a safety and health program to ensure that its
employees have been:
(1) Properly informed of safety practices and
procedures; and
(2) Protected from hazards associated with the
work environment;
(b)
Adopt comprehensive written instructions for the safety of its
employees; and
(c)
Distribute a copy of the written instructions required by (b) above to
each of its employees before assignment to duty in any assignment which
requires handling any energized electrical plant.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 306.05 Resuscitation.
(a)
Each utility shall periodically instruct all employees engaged in work
on electrical plant in accepted safety procedures for resuscitation from
electric shock.
(b)
Each utility shall adopt written safety procedures for resuscitation
from electric shock.
(c)
Each utility shall distribute copies of the written safety procedures
required by this section to each employee who works on any energized plant.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 306.06 Notification of Accidents and Property
Damage.
(a)
A utility shall notify the department in the event of accidents and significant
events involving or potentially involving the utility’s facilities, operations,
works, or systems in accordance with subparts (c) – (f), except during wide
scale emergencies as required by this rule.
(b)
The department shall provide a protocol roster to the utilities updated
as necessary which:
(1) Lists department representatives with their
after work hours telephone contact numbers, email addresses, and text contact
information; and
(2) Lists the general department telephone
number.
(c)
A utility shall notify the department by telephone, automated telephone
notification, or electronic means as soon as possible, but no later than 2
hours after becoming aware of an outage event that interrupts service to more
than 2,000 customers for more than 5 minutes.
(d)
The notification shall include:
(1) The name of the utility;
(2) The name of the person initiating the
notification and a telephone number for call back;
(3) A brief description of the event location;
(4) Estimated number of customers affected; and
(5) Estimated duration of outage or service
restoration time.
(e)
Notification shall be to all department representatives on the protocol
roster, described in (b) above through automated telephone notification, email,
or text.
(f)
A utility shall notify the department by telephone as soon as possible,
but no later than 2 hours after becoming aware of an accident or event that:
(1) Results in serious injury requiring inpatient
hospitalization, or a fatality;
(2) Involves an automobile accident or any other
event, whether caused intentionally or not, that results in a degradation of
operations or safety that affects 500 customers or more with an expected
duration in excess of 12 hours;
(3) Involves a breach of security or threat
against the utility’s facilities addressed in section En 306.10;
(4) Involves aircraft, trains, or commercial
boats;
(5) Results in closure of a state highway; or
(6) Is not covered in this section but has been
reported publicly via major commercial news outlets.
(g)
When an accident or event occurs as described in (f) above, the utility
shall notify the department as follows:
(1) Attempt to contact the appropriate department
representative listed on the protocol roster, described in (b) above, either at
the department telephone number during regular department hours or at the
after-hours number outside of regular department hours;
(2) Proceed sequentially through the roster
attempting to contact a department representative;
(3) If a utility is unable to reach a department
representative after following En 306.06(g)(2) above, the utility shall notify
the department as follows:
a. Call the department general telephone
listing, provided in the protocol roster, and leave a voice mail message:
1. Identifying the utility and the name and
return telephone number of the individual attempting to report; and
2. Stating that an accident or event requiring
notification has occurred and will be reported when the department next opens;
and
b. As soon as possible during regular department
hours, contact the appropriate department representative listed on the protocol
roster, described in (b) above, and proceed sequentially through the roster;
and
(4) When the utility is first able to speak to a
department representative listed on the protocol roster as required by this
section, the utility shall notify the representative of the following:
a. The name of the utility;
b. The name of the person making the report and
the telephone number at which they can be called back;
c. A brief description of the accident or event
and location;
d. A description of any known fatalities,
personal injuries, and damage;
e. Any other known information relevant to the
cause of the accident or event and the extent of the damage; and
f. The time at which:
1. The accident of event occurred; and
2. The utility was first notified or the
accident or event.
(h)
Each utility shall report in writing any accident or event requiring
notification pursuant to (f) above, by completing and submitting to the
department and commission:
(1) Form E-5E, within 5 business days of
notification of the accident or event; and
(2) A more detailed written report, referencing
the original Form E-5E report number, containing any additional supportive
documentation not provided in the original Form E-5E report, within 15 days of
the accident.
(i) When a utility files a report in accordance
with En 306.06(h)(2) and the accident or event involves a utility’s pole or
anchors located within the public way, the utility shall include in its report
whether the poles or anchors were licensed and whether the poles or anchors
were properly located according to that license.
(j)
When a utility files a report in accordance with En 306.06(h)(2) and
death occurs as a direct result of the reported accident, as known to the
utility, the utility shall include this fact in such report.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 306.07 Department Inspection. The department shall inspect the works and system
of each utility as necessary to ensure the manner in which each utility has
conformed and presently conforms to department rules including, without
limitation, with respect to safety policies and procedures, and employee
compliance therewith.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 306.08 Uniform Utility Damage Prevention Program. All utilities shall comply with En 800, the
underground utility damage prevention program rules.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 306.09 Emergency Response Standards and
Electrical Outage Restoration.
(a)
On an annual basis, each utility shall file with the department one
electronic copy of an emergency response plan (ERP).
(b)
ERPs shall incorporate the incident command system and follow the
framework established in the “National Incident Management System,” Third Edition,
dated October 2017, available as noted in Appendix B.
(c)
Utilities shall review and update plans at least once every calendar
year.
(d) Each ERP shall include a clear description of
the responsibilities and policies of senior management during an emergency.
(e)
Each ERP shall provide that one full readiness exercise and one table
top exercise be conducted annually. The
utilities shall invite applicable state agencies and department staff to
participate in such exercises.
(f)
At least annually, the utility shall request to meet with municipal
emergency response personnel to assure the accuracy of emergency response
contact information is shared between the 2 parties, and to validate or revise
the municipalities’ critical infrastructure listing.
(g)
Each ERP shall incorporate projected event levels consistent with Table
306-1:
|
Table 306-1 |
|||
|
Utility |
ERP Event Level |
% Customers Out |
Outage Duration (Hrs.) |
|
|
5 |
≤2 |
<12 |
|
4 |
>2≤5 |
0-24 |
|
|
3 |
>5≤10 |
24-48 |
|
|
2 |
>10≤20 |
48-144 |
|
|
1 |
>20 |
48-240 |
|
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 306.10 Physical and Cyber Security Plans,
Procedures, and Reporting.
(a)
Each utility shall develop, maintain, and follow a written physical
security plan designed to protect the utility’s critical equipment and
facilities from breaches of security.
For purposes of this section, “critical equipment and facilities” means
utility infrastructure without which the utility could not provide safe and
reliable service to its customers.
(b)
The plan shall be risk-based and incorporate:
(1) A threat level assessment;
(2) A list of critical equipment and facilities
to which the plan applies;
(3) Defined security measures for critical
equipment and facilities;
(4) Response procedures and notifications upon
discovery of a breach in security;
(5) Defined process to track events; and
(6) Employee awareness training programs.
(c)
Each utility shall develop, maintain, and follow a written information
cyber security plan designed to protect the utility’s critical cyber
assets. For purposes of this section,
“critical cyber assets” means those electronic data, communications, and
computer network systems without which the utility could not provide safe
reliable service to its customers.
(d)
The plan shall be risk-based and incorporate:
(1) A threat level assessment;
(2) A list of critical cyber assets;
(3) Defined security measures for critical cyber
assets;
(4) Response procedures and notifications upon
discovery of a breach in security;
(5) Defined process to track events; and
(6) Employee awareness training programs.
(e)
Each utility shall submit to the department annually one electronic copy
of each of its physical security plan and cyber security plan. If any such plan contains confidential
information, the utility shall so notify the department in writing to provide
the department with an opportunity to review the confidential information at
the utility’s offices in New Hampshire.
(f)
On the 15th day of the month following the last day of each
quarter, each utility shall file Form E-37 “Quarterly Report of Equipment
Theft, Sabotage, and Breaches of Security,” pursuant to En 308.11 reporting all
material breaches of security as defined within the plans.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
PART
En 307 RECORDS AND REPORTS
En 307.01 Records.
(a)
Each utility shall keep records of the operation and performance of its
generating units and distribution circuits.
(b)
Unless complete information as required by the ISO-NE is furnished by
the utility transmitting the energy at each interconnection point, each utility
receiving electric energy shall maintain adequate instruments and meters to
obtain such complete information as to each delivery.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 307.02 Reports to Department.
(a)
Each utility shall file periodic reports with the department as required
pursuant to En 308 on forms available on the department’s website at www.energy.nh.gov. The utility shall file one electronic copy
with the department as follows:
(1) Each utility shall electronically file each
report, to the extent technologically feasible, in a format compatible with the
computer system of the department; and
(2) For all utilities filing electronic reports,
the filing date shall be deemed to be the date the electronic filing is
received.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 307.03 Interconnection Agreements.
(a)
“Interconnection agreement” means an agreement that sets forth the
contractual terms necessary for any person or entity that generates electricity
to connect to the utility’s system.
(b)
Each utility shall file with the department a copy of each
interconnection agreement entered into by the utility.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 307.04 Reliability Reporting.
(a)
When quarterly circuit or system reliability indices are furnished to
the department, the utility shall include the total number of operations by
device which resulted in an interruption of greater than 5 minutes duration and
the information required by (c) below.
(b)
For purposes of this section, “device” means any equipment designed and
used to automatically operate to remove faulted system elements from the
system.
(c)
Any utility submitting quarterly circuit or system reliability indices
shall also report:
(1) The year and calendar quarter of the report;
(2) The circuit number;
(3) The device identification number;
(4) The type of device operated;
(5) The number of actual operations of the device
in the current reporting quarter, if 2 or more; and
(6) The number of actual device operations in the
current and previous 3 quarters, if 3 or more.
(d)
A utility calculating the number of device operations pursuant to (c)(5)
and (c)(6) above shall exclude:
(1) Operations of devices upstream of the device
being reported; and
(2) Device identification changes due to circuit
reconfigurations.
(e)
Utilities shall not be required to report the information as required in
(a) above for service interruptions that result from wide-scale emergencies.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 307.05 Reporting During Wide-Scale Emergencies.
(a)
Distribution crew reports shall be submitted electronically 4 times per
day at 6 a.m., 10 a.m., 2 p.m., and 8 p.m. using Form E-33 pursuant to En
308.08.
(b)
Transmission crew reports shall be submitted electronically 4 times per
day at 6 a.m., 10 a.m., 2 p.m., and 8 p.m. using Form E-34 pursuant to En
308.09.
(c)
In the event that department staff anticipates the occurrence of a
wide-scale emergency, staff shall notify the utilities and the utilities shall
file crew reports prior to the onset of the wide-scale emergency. Event names shall be determined by the
department and made known to each of the utilities required to report.
(d)
Crew reporting shall consist of only those crews which are physically
located within the state boundaries regardless of what their work status is
such as sleeping, resting, eating, or restoration of circuits, and shall
reflect the crews which are available for restoration at the time of the
report.
(e)
Crew reporting shall be completed for front line, field assessment, and
public safety functions and as described in Forms E-33 and E-34.
(f)
Electric utility outage reports shall be submitted to the department
using applicable Forms E-36A, E-36B, and E-36C any
time outage information is not publicly available on utility websites during
wide-scale emergencies pursuant to En 308.10.
(g)
Electric utility outage reports as described in (f) above shall be
submitted at the same times as required in (a) and (b) above or upon request of
department staff.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 307.06 Reporting of Reliability Measures.
(a)
For purposes of this section, the following definitions shall apply:
(1) “Customer average interruption duration index
(CAIDI)” means the average interruption duration or average time to restore
service per interrupted customer and shall be presented as the following ratio:
Total sum of customer interruption durations/total number of customer
interruptions;
(2) “System average interruption frequency index
(SAIFI)” means the average number of interruptions per customer and shall be
presented in the following ratio: Total number of customer
interruptions/average number of customers served;
(3) “System average interruption duration index
(SAIDI)” means the average duration of customer interruptions and shall be
presented as the following calculation: SAIDI = CAIDI x SAIFI;
(4) “CIII” means the average number of customers
without power per interruption index as determined by dividing the number of
customers interrupted by the number of interruptions;
(5) “TMED” means the threshold value used to
determine a major event day as defined in IEEE 1366-2022, Section 1.5 “Guide
for Electric Power Distribution Reliability Indices,” dated 11/22/2022,
available as noted in Appendix B; and
(6) “Major event day” means a day during which a
utility’s daily system SAIDI exceeds the TMED.
(b)
Within 45 days of the end of each calendar quarter, each utility shall
file quarterly reports of reliability measures defined in (a)(1) - (4) above,
and shall separately report the reliability measures by area work center and as
aggregated for the whole company.
(c)
Each utility shall report the indices separately:
(1) With all interruptions included in the data;
and
(2) With major event days excluded from the data.
(d)
The report shall depict the reliability measure information by
distribution and transmission systems as applicable.
En 307.07 Tree-Pruning Standards.
(a)
With the landowner’s consent, utilities shall prune trees adjacent to
all distribution circuits to the following minimum clearances on no more than a
5-year cycle:
(1) Ten feet below the conductors;
(2) Eight feet to the side of the nearest
conductor; and
(3) Fifteen feet above the conductors, at time of
pruning.
(b)
Utilities shall implement measures such as mid-cycle reviews to identify
and mitigate elevated risk from tree exposure on circuits or sections of
circuits that are significantly or continually experiencing tree-related
interruptions, where it is practical to do so.
(c)
Utilities shall not be required to prune to the clearance standards
specified in (a) of this section where:
(1) The landowner has refused or restricted
permission to prune;
(2) A municipality or other local governing body,
by ordinance or other official means, has refused or restricted permission to
prune; or
(3) Pruning to the standards specified in subpart
(a) would be detrimental to the health of the tree, in which the utility shall
adhere to the guidelines provided in ANSI A300 (Part 1) “Tree Care Operations –
Tree, Shrub and Other Woody Plant Maintenance – Standard Practices” (2017),
available as noted in Appendix B.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
PART En 308 FORMS REQUIRED BY ALL UTILITIES
En 308.01 E-1 Monthly Report on Voltage Complaints. Each utility shall on a monthly basis
complete a report of voltage complaints on Form E-1 dated 10/2024, available at
the department’s website at www.energy.nh.gov,
and file one signed electronic copy with the department.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 308.02 E-2 Quarterly Report on Interruptions of
Service Over 5 Minutes Duration.
Each utility shall on a quarterly basis complete a report of service
interruptions of more than 5 minutes on the Form E-2 dated 10/2024, available at the department’s website at www.energy.nh.gov, and file one signed
electronic copy with the department.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 308.03 E-3 Annual Report of Total Electric Meter
Tests. Each utility shall on an
annual basis complete a report of total electric meter tests on Form E-3 dated
10/2024, available at the department’s website at www.energy.nh.gov, and file one signed
electronic copy with the department.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 308.04 E-3A Report on Selective Sample Tests of
Weighted Average Accuracy on Self-Contained Single-Phase Meters and Network
Meters. Each utility shall on an
annual basis complete a report on selected sample tests of weighted average
accuracy on self-contained single-phase meters and network meters on Form E-3A
dated 10/2024, available at the department’s website at www.energy.nh.gov, and file one signed
electronic copy with the department.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 308.05 E-4 Monthly Report on Electric Meter
Complaint Tests. Each utility shall
on a monthly basis complete a report of electric meter complaint tests on Form
E-4 dated 10/2024, available at the department’s website at www.energy.nh.gov, and file one signed
electronic copy with the department.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 308.06 E-5E Utility Accident Report. Each utility shall report any accident or
event to the department by completing an accident report on Form E-5E dated
10/2024, available at the department’s website at www.energy.nh.gov, and file one signed
electronic copy with the department. The
utility shall provide the following information in addition to the completed
form:
(a) If “Five Day
Report” is checked, immediate or next day notification as defined by En 306.06
is required, followed by Form E-5E being filed within 5 business days of the
accident. A detailed report shall follow
within 15 days of the accident;
(b)
If death occurs within 60 days following the reported accident as a
direct result of the accident, and is known by the utility, after this report
is filed, that fact shall be stated in an additional report; and
(c)
If answering “No” to “Pole/Anchor Information,” attach license and a
diagram of the actual location versus the licensed location.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 308.07 F-22
Information Sheet. Each utility
shall, on an annual basis or when there are changes to information previously
provided, complete and file with the department one signed electronic copy of
Form F-22 dated 10/2024, available at the department’s website at www.energy.nh.gov.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 308.08 E-33 Distribution Crew Report. During wide scale emergencies, a utility
shall complete Form E-33 dated 10/2024, available at the department’s website
at www.energy.nh.gov,
and file one electronic copy with the department.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 308.09 E-34 Transmission Crew Report. During wide scale emergencies, a utility
shall complete Form E-34 dated 10/2024, available at the department’s website
at www.energy.nh.gov,
and file one electronic copy with the department.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 308.10 E-36A,
E-36B, and E-36C Electric
Utility Outage Report. During wide
scale emergencies, each utility shall complete the applicable Form E-36 dated
10/2024, available at the department’s website at www.energy.nh.gov, and file one electronic
copy with the department as follows:
(a)
E-36A - Granite State Electric Company d/b/a/ Liberty;
(b)
E-36B - Public Service Company of New Hampshire d/b/a Eversource Energy;
and
(c)
E-36C - Unitil Energy Systems, Inc.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 308.11 Quarterly Report of Equipment Theft,
Sabotage, and Breaches of Security.
Each utility shall on a quarterly basis complete a report of equipment
theft, sabotage, and breaches of security on Form E-37 dated 10/2024, available
at the department’s website at www.energy.nh.gov,
and file one signed electronic copy with the department.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
En 308.12 Quarterly Reporting of Electric Utility
Reliability Measures. Each utility
shall on a quarterly basis complete a report of
electric utility reliability measures on Form E-38 dated 10/2024, available at the department’s website at www.energy.nh.gov, and file one signed
electronic copy with the department.
Source. #14101, eff 10-22-24, EXPIRES: 10-22-34 (see
Revision Note at chapter heading for En 300)
APPENDIX A
|
Rule |
Statute |
|
En
301.01-En 301.02 |
RSA
12-P:5, IV; RSA 362:2, II |
|
En
302.01-En 302.24 |
RSA
12-P:5, IV; RSA 370:1-9 |
|
En
303.01 |
RSA
12-P:5, IV; RSA 374:15 |
|
En
303.02 |
RSA
12-P:5, IV |
|
En
304.01-En 304.04 |
RSA
12-P:5, IV; RSA 370:1 , RSA 370:2; RSA 374:1;RSA 374-F:3, I |
|
En
305.01-En 305.07 |
RSA
12-P:5, IV; RSA 365:6; RSA 370:1-9, RSA 374:1, RSA 374-F:3, I |
|
En
306.01-En 306.05 |
RSA
12-P:5, IV; RSA 374:1; RSA 374-F:3, I |
|
En
306.06 and En 306.07 |
RSA
12-P:5, IV; RSA 365:6; RSA 374:39 |
|
En
306.08 |
RSA
12-P:5, IV, RSA 374:1, RSA 374-F:3, I; RSA 374:49 |
|
En
306.09-En 306.10 |
RSA
12-P:5, IV; RSA 374:1, and RSA 374:3 |
|
En
307.01-En 307.04 |
RSA
12-P:5, IV |
|
En
307.05-En 307.07 |
RSA
12-P:5, IV |
|
En
308.01-En 308.02 |
RSA
12-P:5, IV; RSA 374:15 |
|
En
308.03-En 308.05 |
RSA
12-P:5, IV; RSA 370:1-9; RSA 374:15 |
|
En
308.06 |
RSA
12-P:5, IV; RSA 374:15; RSA 374:39 |
|
En
308.07 |
RSA
12-P:5, IV; RSA 374:4, RSA 374:5; RSA
374:15 |
|
En
308.08-En 308.10 |
RSA
12-P:5, IV; RSA 374:1; RSA 374:4; RSA 374:15 |
|
En
308.11–En 308.12 |
RSA
12-P:5, IV; RSA 374:1; RSA 374:15; RSA 374-F:3, I |
APPENDIX B: INCORPORATION BY REFERENCE INFORMATION
|
RULE |
TITLE (DATE) |
SOURCE |
|
En
302.18 En
306.01(b)(1) En
307.06(a)(5) |
IEEE
141-1993 “Recommended Practice For Electric Power Distribution For Industrial
Plants,” section 8.2.1, dated 4/29/1994 IEEE
C2-2023 “National Electrical Safety Code,” 2023 Edition IEEE
1366-2022, Section 1.5 “Guide For Electric Power Distribution Reliability
Indices,” dated 11/22/2022 |
Hard
copy can be purchased for $234 and a PDF version for $209 at: http://techstreet.com/ieee Hard
copy can be purchased for $237 and a PDF version for $214 at: http://techstreet.com/ieee Hard
copy can be purchased for $84 and a secure pdf for $68 at: http://techstreet.com/ieee Institute
of Electrical and Electronic Engineers Operation Center, 445 Hoes Lane,
Piscataway, NJ 08854-4141 |
|
En
304.02(g) En
305.02(d) En
305.02(f)(4) En
305.03(a) En
305.03(a) En
307.07(c)(3) |
ANSI
C84.1-2020 “Electric Power Systems Voltage Ratings (60 Hz),” dated 3/10/2020 ANSI
C12.1-2022 “Code for Electricity Metering,” dated 6/9/2022 ANSI
C12.20-2015 “Electricity Meters,” dated 4/1/2017 ANSI
A300 (Part 1) “Tree Care Operations – Tree, Shrub and Other Woody Plant
Maintenance – Standard Practices” (2017) |
PDF
copy can be purchased for $163 at: https://webstore.ansi.org/ PDF
copy can be purchased for $465 at: https://webstore.ansi.org/ Included with ANSI C12.1-2022,
above. American
National Standards Institute 25
West 43rd Street, 4th Floor, New York, NY 10036 Paper
copy can be purchased for $79 at: https://www.amazon.com/Pruning-Standard-Shrub-Maintenance-Practises/dp/B007SY2KJK |
|
En
306.09(b) |
“National
Incident Management System,” Third Edition dated October 2017 |
Can be obtained at no cost at: http://www.fema.gov/national-incident-management-system Federal Emergency Management Agency U.S. Dept. of Homeland Security 500 C Street SW Washington, DC 20472 |